Download
Thermo-Chiller Standard Type Water Cooled 200 V / 400 V Specification HRSH090 Series – Temperature SMC – Điều Hoà Không Khí SMC
Thermo-Chiller Standard Type Water-Cooled 200 V Specification HRS090 Series Specifications
HRS090 series external appearance
Model | HRS090-W□-20-□ | ||
---|---|---|---|
Cooling Method | Water-cooled refrigeration type | ||
Refrigerant | R410A (HFC) | ||
Refrigerant Charge (kg) | 1.15 | ||
Control Method | PID control | ||
Ambient Operating Temperature / Humidity / Altitude*1 *2 | Temperature: 5 to 45°C, Humidity: 30 to 70%, Altitude: Less than 3,000 m | ||
Circulating Fluid System | Circulating Fluid*3 | Clear water, 15% ethylene glycol aqueous solution, deionized water (pure water) | |
Set Temperature Range*2 (°C) | 5 to 35 | ||
Cooling Capacity 50/60 Hz*4 (kW) | 9.0/10.5 | ||
Heating Capacity*5 (kW) | 1.7/2.2 | ||
Temperature Stability*6 (°C) | ±0.5 | ||
Pump Capacity | Rated Flow Rate 50/60 Hz (Discharge Outlet)*7 (L/min) | 29/45 | |
Maximum Flow Rate 50/60 Hz (L/min) | 55/68 | ||
Maximum Pump Head (m) | 50 | ||
Minimum Required Flow Rate 50/60 Hz*8 (L/min) | 29/45 | ||
Tank Capacity (L) | 18 | ||
Circulating Fluid Outlet, Circulating Fluid Inlet Pipe Connection Port Diameter | Rc 1 (symbol F: G 1, symbol N: NPT 1) | ||
Drain Port Pipe Connection Port Diameter | Rc 1/4 (symbol F: G 1/4, symbol N: NPT 1/4) | ||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), brass, bronze, PTFE FKM, EPDM, PVC, NBR, POM, PE, PP, carbon, ceramic |
||
Heat-Dissipating Water System | Temperature Range (°C) | 5 to 40 | |
Pressure Range (MPa) | 0.3 to 0.5 | ||
Required Flow Rate 50/60 Hz (L/min) | 25/25 | ||
Inlet-Outlet Pressure Differential of Heat-Dissipating Water (MPa) | 0.3 or more | ||
Heat-Dissipating Water Inlet, Heat-Dissipating Water Outlet Pipe Connection Port Diameter | Rc 1/2 (symbol F: G 1/2, symbol N: NPT 1/2) | ||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, brass, PTFE, NBR, EPDM | ||
Electrical Systems | Power Supply | Three-phase 200 V AC (50 Hz), three-phase 200 to 230 V AC (60 Hz) Allowable voltage variation ±10% (no continuous voltage variation) |
|
Compatible Earth Leakage Circuit Breaker*9 | Rated Current (A) | 30 | |
Current Sensitivity (mA) | 30 | ||
Rated Operating Current 50/60 Hz*6 (A) | 13/14 | ||
Rated Power Consumption 50/60 Hz*6 kW (kVA) | 3.3/4.2 (4.4/4.9) | ||
Noise Level (Front 1 m, Height 1 m)*6 (dB [A]) | 65 | ||
Accessories | Alarm code list sticker 2 pcs. (1 Japanese, 1 English) Operation manual (for installation and operation) 2 pcs. (1 Japanese, 1 English) Y-strainer (40 mesh) 25A, barrel nipple 25A Anchor bolt mounting brackets 2 pcs. (including M10 bolts 4 pcs.)*10 |
||
Weight (Dry State) (kg) | Approx. 124 |
*1: Use in a condensation-free environment.
*2: If the ambient operating temperature or circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution. In addition, if there is a possibility that the heat dissipating water could freeze, make sure to drain the heat-dissipating water from the heat-dissipating circuit.
*3: Use circulating fluid that meets the following conditions. In addition, if there is a possibility that the heat dissipating water could freeze, make sure to drain the heat-dissipating water from the heat-dissipating circuit.
Clear water: Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994)
15% ethylene glycol aqueous solution: Diluted with clear water, no preservatives or additives
Deionized water (pure water): Electrical conductivity 1 μS/cm or more (electrical resistance 1 MΩ/cm or less)
*4: 1. Heat-dissipating water temperature: 32°C, 2. Circulating fluid: clear water, 3. Circulating fluid temperature: 20°C, 4. Circulating fluid flow rate: rated flow rate, 5. Power supply: 200/400 V AC
*5: 1. Heat-dissipating water temperature: 32°C, 2. Circulating fluid: clear water, 3. Circulating fluid flow rate: rated flow rate, 4. Power supply: 200/400 V AC
*6: 1. Heat-dissipating water temperature: 32°C, 2. Circulating fluid: clear water, 3. Circulating fluid temperature: 20°C, 4. Load: listed cooling capacity, 5. Circulating fluid flow rate: rated flow rate, 6. Power supply: 200/400 V AC, 7. Pipe length: shortest
*7: When circulating fluid outlet pressure = 0.5 MPa
*8: Flow rate necessary to maintain cooling capacity and keep the circulating fluid outlet pressure at 0.5 MPa or less. Install bypass piping when below the minimum required flow rate.
*9: To be provided by the customer. Option B [With earth leakage circuit breaker] has the described earth leakage circuit breaker built in.
*10: The anchor bolt fixing brackets (M10 bolts 4 pcs.) are used for fixing to wooden skids when packaging the Thermo-Chiller. Anchor bolts are not included.
Thermo-Chiller Standard Type Water Cooled 200 V / 400 V Specification HRSH090 Series – Temperature SMC – Điều Hoà Không Khí SMC
HRS090-W-20
HRS090-W-20-J
HRS090-W-20-W
HRS090-W-40
HRS090-W-40-J
HRS090-W-40-JM
HRS090-W-40-M
HRS090-WF-20-BJM
HRS090-WF-40
HRS090-WN-20-BJ
HRS090-WN-20-BJW
HRS090-WN-20-BM
HRS090-WN-20-M
Liên Hệ Medin Co., Ltd
- Công ty TNHH Mễ Đình được thành lập từ năm 2006.
- Là Đại lý uỷ quyền của Weller tại Việt Nam.
- Từ đó đến nay Medin luôn là Công ty dẫn đầu về lĩnh vực Tự Động Hoá ở thị trường trong và ngoài nước với hơn 1,000 khách hàng, cùng với rất nhiều dự án lớn nhỏ cho các nhà máy sản xuất.
- Chúng tôi cung cấp cho khách hàng những giải phát tuyệt vời nhất trong việc ứng dụng Tự Động Hoá vào sản xuất
- Phương châm: “Giải pháp của chúng tôi, lợi ích của khách hàng”
- Giá trị cốt lõi: “Uy tín là sự tồn tại của chúng tôi”
- Hơn 20 năm kinh nghiệm, chúng tôi có đội ngũ kỹ sư nhiều kinh nghiệm, có khả năng tư vấn, đưa ra giải pháp có lợi nhất cho khách hàng.
- Sự tin tưởng và đồng hành của khách hàng là động lực để Medin phát triển cao hơn và xa hơn.
👉 Công ty Medin hỗ trợ:
Tư vấn giải pháp tối ưu
Có sẵn sản phẩm dùng thử
Hỗ trợ test tận nơi
👉 Nếu bạn có bất kỳ yêu cầu nào, vui lòng liên hệ với chúng tôi.
☎️ Hotline: 0902782082
🌐 Website: https://www.medin.com.vn/
- VP Ho Chi Minh: 01 Đường 410C, Phước Long A, Tp. Thủ Đức
- Ha Noi Branch: 562 Nguyễn Văn Cừ, Long Biên, Hà Nội
- Da Nang Branch: 63 Phan Đăng Lưu, Hải Châu, Đà Nẵng